22kV and 35kV AAC ACSR XLPE Overhead Cable for Myanmar
22kV 35kV AAC ACSR XLPE Cable
22kV ACSR-CX, 35kV ACSR-CX
22kV AL-CX, 35kV AL-CX
22kV ACSR-X, 35kV ACSR-X
22kV AL-X, 35kV AL-X
22kV 35kV AAC ACSR XLPE Overhead Cable For Myanmar
Konstruktion: Alle aluminiumsleder, Aluminiumsleder stålforstærket (ACSR), featuring stranded aluminum conductors and galvanized steel reinforcement, along with Semi-Conducting Screened Cross-Linked Polyethylene (XLPE) Insulation Power Cable.
Option: The stranded conductor layer shall be filled with water-blocking material.
Anvendelse: Suitable for overhead power transmission and distribution lines.

22kV ACSR-CX (BS EN 50397-1)
Leder | Tykkelse of Insulation | Ca.. overall Diameter | Ca.. Samlet set Vægt | Min. Breaking Load | Max.D.C. Leder Modstand(20℃) | |||
Gross Sectional Areal | Na.and Diameter of wires(Al) | Na. and Diameter of wires(Stål) | Outside Diameter | |||||
mm2 | mm | mm | mm | mm | mm | kg/km | kN | Ω/ km |
50/8 | 6/3.20 | 1/3.20 | 9.6 | 2.5 | 17 | 330 | 17.112 | 0.5951 |
70/11 | 6/3.80 | 1/3.80 | 11.4 | 2.5 | 18 | 430 | 24.13 | 0.4218 |
95/16 | 6/4.50 | 1/4.50 | 13.5 | 2.5 | 20 | 560 | 33.369 | 0.3007 |
120/19 | 26/2.40 | 7/1.85 | 15.15 | 2.5 | 22 | 660 | 41.521 | 0.244 |
150/19 | 24/2.80 | 7/1.85 | 16.75 | 2.5 | 24 | 760 | 46.307 | 0.2046 |
150/24 | 26/2.70 | 7/2.10 | 17.1 | 2.5 | 24 | 810 | 52.279 | 0.2039 |
185/24 | 24/3.15 | 7/2.10 | 18.9 | 2.5 | 26 | 930 | 58.075 | 0.154 |
185/29 | 26/2.98 | 7/2.30 | 18.82 | 2.5 | 26 | 960 | 62.055 | 0.1519 |
240/32 | 24/3.60 | 7/2.40 | 21.6 | 2.5 | 29 | 1180 | 75.05 | 0.1182 |
300/39 | 24/4.00 | 7/2.65 | 23.95 | 2.5 | 31 | 1410 | 90.574 | 0.0958 |
330/43 | 54/2.80 | 7/2.80 | 25.2 | 2.5 | 32 | 1550 | 103.784 | 0.0869 |
400/51 | 54/3.05 | 7/3.05 | 27.5 | 2.5 | 35 | 1810 | 120.481 | 0.0733 |
35kV ACSR-CX (BS EN 50397-1)
Leder | Tykkelse of Isolering | Ca.. overall Diameter | Ca.. Samlet set Vægt | Min. Breaking Load | Max.D.C. Leder Modstand(20℃) | |||
Gross Sectional Areal | Na.and Diameter of wires(Al) | Na. and Diameter of wires(Stål) | Outside Diameter | |||||
mm2 | mm | mm | mm | mm | mm | kg/km | kN | Ω/ km |
50/8 | 6/3.20 | 1/3.20 | 9.6 | 3.9 | 19 | 400 | 17.112 | 0.5951 |
70/11 | 6/3.80 | 1/3.80 | 11.4 | 3.9 | 21 | 510 | 24.13 | 0.4218 |
95/16 | 6/4.50 | 1/4.50 | 13.5 | 3.9 | 23 | 650 | 33.369 | 0.3007 |
120/19 | 26/2.40 | 7/1.85 | 15.15 | 3.9 | 25 | 760 | 41.521 | 0.244 |
150/19 | 24/2.80 | 7/1.85 | 16.75 | 3.9 | 26 | 860 | 46.307 | 0.2046 |
150/24 | 26/2.70 | 7/2.10 | 17.1 | 3.9 | 27 | 910 | 52.279 | 0.2039 |
185/24 | 24/3.15 | 7/2.10 | 18.9 | 3.9 | 29 | 1040 | 58.075 | 0.154 |
185/29 | 26/2.98 | 7/2.30 | 18.82 | 3.9 | 29 | 1070 | 62.055 | 0.1519 |
240/32 | 24/3.60 | 7/2.40 | 21.6 | 3.9 | 31 | 1300 | 75.05 | 0.1182 |
300/39 | 24/4.00 | 7/2.65 | 23.95 | 3.9 | 34 | 1540 | 90.574 | 0.0958 |
330/43 | 54/2.80 | 7/2.80 | 25.2 | 3.9 | 35 | 1690 | 103.784 | 0.0869 |
400/51 | 54/3.05 | 7/3.05 | 27.5 | 3.9 | 37 | 1960 | 120.481 | 0.0733 |
22kV AL-CX (BS EN 50397-1)
Leder | Tykkelse of Isolering | Apprax. Samlet set Diameter | Approx. Overalal Vægt | Min. Breaking Load | Max.D.C. Leder Modstand(20℃) | ||
Coss Sectional Areal | Na. and Diameter of wires | Outside Diameter | |||||
mm2 | mm | mm | mm | mm | kg/km | kN | Ω/ km |
25 | 7/2.13 | 6.39 | 2.5 | 13 | 170 | 4.5 | 1.1489 |
35 | 7/2.51 | 753 | 2.5 | 15 | 200 | 5.913 | 0.8347 |
50 | 7/3.00 | 9 | 2.5 | 16 | 260 | 8.198 | 0.5748 |
70 | 7/3.55 | 10.65 | 2.5 | 17 | 330 | 11.288 | 0.4131 |
95 | 7/4.10 | 12.3 | 25 | 19 | 410 | 14.784 | 0.3114 |
120 | 19/2.80 | 14 | 2.5 | 21 | 500 | 19.89 | 0.2459 |
150 | 19/3.15 | 15.75 | 2.5 | 23 | 600 | 24.42 | 0.1944 |
185 | 19/3.50 | 17.5 | 25 | 24 | 720 | 29.832 | 0.1574 |
240 | 19/4.00 | 20 | 25 | 27 | 900 | 38.192 | 0.1205 |
300 | 37/3.15 | 22.05 | 2.5 | 29 | 1050 | 47.569 | 0.1 |
400 | 37/3.66 | 25.62 | 2.5 | 33 | 1360 | 63.42 | 0.074 |
35kV AL-CX (BS EN 50397-1)
Leder | Diámetro exterior aproximado mm | Conductor de mensajería (Ehs) | Peso aproximado kg/km | ||||
Antal nominelle tværsnit af kerner N.° × mm² | Antal kabler (min) | Diámetro nominal del conductor mm | N.º de trenzado × mm | Diámetro del conductor mensajero mm | Carga mínima de rotura kN | ||
3X1X35 | 6 | 6.9 | 54.1 | 7×3.00 | 9 | 64.36 | 2337 |
3X1X50 | 6 | 8.1 | 67.9 | 7×2.64 | 7.92 | 49.82 | 3208 |
3X1X70 | 12 | 9.8 | 71.5 | 7×2.64 | 7.92 | 49.82 | 3577 |
3X1X95 | 15 | 11.4 | 75.4 | 7×3.68 | 11.04 | 92.82 | 4339 |
3X1X120 | 15 | 12.8 | 78.4 | 7×3.68 | 11.04 | 92.82 | 4703 |
3X1X150 | 15 | 14.4 | 82.3 | 19×2.86 | 14.29 | 149.9 | 5571 |
3X1X185 | 30 | 16 | 86.2 | 19×2.86 | 14.29 | 149.9 | 6093 |
3X1X240 | 30 | 18.4 | 91.3 | 19×2.86 | 14.29 | 149.9 | 6854 |
22kV ACSR-X (BS EN 50397-1)
Leder | Tykkelse of Isolering | Ca.. overall Diameter | Ca.. Samlet set Vægt | Min. Breaking Load | Max.D.C. Leder Modstand(20℃) | |||
Gross Sectional Areal | Na.and Diameter of wires(Al) | Na. and Diameter of wires(Stål) | Outside Diameter | |||||
mm2 | mm | mm | mm | mm | mm | kg/km | kN | Ω/ km |
50/8 | 6/3.20 | 1/3.20 | 9.6 | 3.5 | 17 | 340 | 17.112 | 0.5951 |
70/11 | 6/3.80 | 1/3.80 | 11.4 | 3.5 | 19 | 440 | 24.13 | 0.4218 |
95/16 | 6/4.50 | 1/4.50 | 13.5 | 3.5 | 21 | 570 | 33.369 | 0.3007 |
120/19 | 26/2.40 | 7/1.85 | 15.15 | 3.5 | 23 | 680 | 41.521 | 0.244 |
150/19 | 24/2.80 | 7/1.85 | 16.75 | 3.5 | 24 | 780 | 46.307 | 0.2046 |
150/24 | 26/2.70 | 7/2.10 | 17.1 | 3.5 | 25 | 830 | 52.279 | 0.2039 |
185/24 | 24/3.15 | 7/2.10 | 18.9 | 3.5 | 26 | 950 | 58.075 | 0.154 |
185/29 | 26/2.98 | 7/2.30 | 18.82 | 3.5 | 26 | 970 | 62.055 | 0.1519 |
240/32 | 24/3.60 | 7/2.40 | 21.6 | 3.5 | 29 | 1195 | 75.05 | 0.1182 |
300/39 | 24/4.00 | 7/2.65 | 23.95 | 3.5 | 32 | 1430 | 90.574 | 0.0958 |
330/43 | 54/2.80 | 7/2.80 | 25.2 | 3.5 | 33 | 1570 | 103.784 | 0.0869 |
400/51 | 54/3.05 | 7/3.05 | 27.5 | 3.5 | 35.1 | 1830 | 120.481 | 0.0733 |
35kV ACSR-X (BS EN 50397-1)
Leder | Tykkelse of Isolering | Ca.. overall Diameter | Ca.. Samlet set Vægt | Min. Breaking Load | Max.D.C. Leder Modstand(20℃) | |||
Gross Sectional Areal | Na.and Diameter of wires(Al) | Na. and Diameter of wires(Stål) | Outside Diameter | |||||
mm2 | mm | mm | mm | mm | mm | kg/km | kN | Ω/ km |
50/8 | 6/3.20 | 1/3.20 | 9.6 | 55 | 21 | 450 | 17.112 | 0.5951 |
70/11 | 6/3.80 | 1/3.80 | 11.4 | 55 | 23 | 560 | 24.13 | 0.4218 |
95/16 | 6/4.50 | 1/4.50 | 13.5 | 55 | 25 | 710 | 33.369 | 0.3007 |
120/19 | 26/2.40 | 7/1.85 | 15.15 | 55 | 27 | 820 | 41.521 | 0.244 |
150/19 | 24/2.80 | 7/1.85 | 16.75 | 55 | 28 | 930 | 46.307 | 0.2046 |
150/24 | 26/2.70 | 7/2.10 | 17.1 | 55 | 29 | 980 | 52.279 | 0.2039 |
185/24 | 24/3.15 | 7/2.10 | 18.9 | 5.5 | 30 | 1110 | 58.075 | 0.154 |
185/29 | 26/2.98 | 7/2.30 | 18.82 | 55 | 30 | 1130 | 62.055 | 0.1519 |
240/32 | 24/3.60 | 7/2.40 | 21.6 | 5.5 | 33 | 1370 | 75.05 | 0.1182 |
300/39 | 24/4.00 | 7/2.65 | 23.95 | 55 | 36 | 1630 | 90.574 | 0.0958 |
330/43 | 54/2.80 | 7/2.80 | 25.2 | 55 | 37 | 1770 | 103.784 | 0.0869 |
400/51 | 54/3.05 | 7/3.05 | 27.5 | 55 | 39 | 2050 | 120.481 | 0.0733 |
22kV AL-X (BS EN 50397-1)
Leder | Tykkelse of Isolering | Ca.. Samlet set Diameter | Ca.. Samlet set Vægt | Min. Breaking Load | Max.D.C Leder Modstand(20℃ | ||
Coss Sectional Areal | Na. and Diameter of wires | Outside Diameter | |||||
mm2 | mm | mm | mm | mm | kg/km | kN | Ω/ km |
25 | 7/2.13 | 6.39 | 3.5 | 14 | 180 | 4.5 | 1.1489 |
35 | 7/2.51 | 7.53 | 3.5 | 15 | 220 | 5.913 | 0.8347 |
50 | 7/3.00 | 9 | 3.5 | 16 | 270 | 8.198 | 0.5748 |
70 | 7/3.55 | 10.65 | 3.5 | 18 | 350 | 11.288 | 0.4131 |
95 | 7/4.10 | 12.3 | 3.5 | 20 | 430 | 14.784 | 0.3114 |
120 | 19/2.80 | 14 | 3.5 | 22 | 510 | 19.89 | 0.2459 |
150 | 19/3.15 | 15.75 | 3.5 | 23 | 620 | 24.42 | 0.1944 |
185 | 19/3.50 | 17.5 | 3.5 | 25 | 730 | 29.832 | 0.1574 |
240 | 19/4.00 | 20 | 3.5 | 28 | 910 | 38.192 | 0.1205 |
300 | 37/3.15 | 22.05 | 3.5 | 30 | 1075 | 47.569 | 0.1 |
400 | 37/3.66 | 25.62 | 3.5 | 33 | 1390 | 63.42 | 0.074 |
35kV AL-X (BS EN 50397-1)
Leder | Tykkelse of Isolering | Ca.. Samlet set Diameter | Ca.. Samlet set Vægt | Min. Breaking Load | Max.D.C Leder Modstand(20℃) | ||
Cross Sectional Areal | Na. and Diameter of wires | Outside Diameter | |||||
mm2 | mm | mm | mm | mm | kg/km | kN | Ω/ km |
25 | 7/2.13 | 6.39 | 5.5 | 18 | 272 | 4.5 | 1.1489 |
35 | 7/2.51 | 7.53 | 5.5 | 19 | 317 | 5.913 | 0.8347 |
50 | 7/3.00 | 9 | 5.5 | 21 | 382 | 8.198 | 0.5748 |
70 | 7/3.55 | 10.65 | 5.5 | 22 | 463 | 11.288 | 0.4131 |
95 | 7/4.10 | 12.3 | 5.5 | 24 | 554 | 14.784 | 0.3114 |
120 | 19/2.80 | 14 | 5.5 | 26 | 651 | 19.89 | 0.2459 |
150 | 19/3.15 | 15.75 | 5.5 | 27 | 765 | 24.42 | 0.1944 |
185 | 19/3.50 | 17.5 | 5.5 | 29 | 889 | 29.832 | 0.1574 |
240 | 19/4.00 | 20 | 5.5 | 32 | 1084 | 38.192 | 0.1205 |
300 | 37/3.15 | 22.05 | 5.5 | 34 | 1258 | 47.569 | 0.1 |
400 | 37/3.66 | 25.62 | 5.5 | 37 | 1595 | 63.42 | 0.074 |
22kV and 35kV AAC ACSR XLPE Overhead Cable for Myanmar
22kV 35kV AAC ACSR XLPE
Power grids: To transmit electrical power from power generation plants to substations and then to distribution networks, cable could be used in underground or overhead installations.
Industrial applications: In factories, mines, and other industrial settings, the cable could be used to connect electrical equipment, motors, transformers, and other components within the facility’s power distribution system.
Infrastructure projects: For large-scale infrastructure projects such as airports, tunnels, bridges, and road networks, cable can be specified for its durability, waterproofing, og modstand mod miljøfaktorer.
Renewable energy systems: In wind farms, solar farms, and other renewable energy generation facilities, the cable could be used to connect turbines, panels, and other power generating units to the main power grid.
Utility networks: Utilities, including water, gas, and electric utilities, often use specialized cables in their networks. The cable could be tailored to specific requirements within these networks, such as increased fire resistance, low smoke emission, or resistance to chemicals and other environmental hazards.
Marine and Offshore Installations: Due to its potential impermeability and resistance to saltwater corrosion, the cable could be suitable for use in marine and offshore environments, such as connecting offshore wind turbines, submarine cables, or subsea power distribution systems.
It is important to note that the exact specifications and capacities of the cable will depend on the manufacturer and the specific application requirements. Always consult the manufacturer’s technical documentation and specifications before selecting and using the cable.