1/0-1/0-1/0 Bergen Aluminum XLPE URD Triplex Direct Burial Cable It is intended for use in secondary distribution circuits, being suitable for installation in conduits or for direct burial applications. Maximum operating temperature should not exceed 90°C in wet and dry locations. The nominal voltage is 600 volts. As an option, This cable can be delivered pre-installed in conduit.
Also know as: bergen aluminum urd cable 1/0-1/0-1/0, urd bergen direct burial cable 1/0-1/0-1/0, tres bergen 1/0-1/0-1/0 Cable conductor, cable triplex Bergen 1/0-1/0-1/0, cable triplex Bergen 1/0-1/0-1/0, Bergen triplex aluminum underground cable 1/0-1/0-1/0 , 1/0-1/0-1/0 power cord 3 bergen drivers, 1/0-1/0-1/0 plywood the aluminum mountains, 1/0-1/0-1/0 bergen underground triplex, 1/ 0-1/0-1/0 bergen triplex underground cable, 1/0-1/0-1/0 bergen triplex underground cable, 1/0-1/0-1/0 direct burial triplex bergen, 1/0- Conductor triplex bergen 1/0-1/0, Bergen direct burial electrical cable 1/0-1/0-1/0, bergen direct burial power cable 1/0-1/0-1/0, 1/0-1 /0-1/0 Bergen Aluminum Direct Burial Cable.
Standard of 1/0-1/0-1/0 Bergen Aluminum XLPE URD triplex Direct Burial Cable
ICEA S-105-6922 Standard for Specification of Control Cables, thermocouple extension and instrumentation.
ASTM B-230 Standard Specification for 1350-H19 Aluminum Wire for Electrical Purposes
ASTM B-609 Standard Specification for Aluminum Round Wire 1350, annealed and intermediate tempering, for electrical purposes
ASTM B-231 Standard Specification for Aluminum Conductor 1350 concentric braids
ASTM B-901 Standard Specification for Compressed Round Stranded Aluminum Conductor, supported in coated steel (ACSR/TW)
Accepted by Russia Accepted by the Rural Public Utilities Service
Federal Specification J-C-30 B Federal Specification for Cables, energy, electricity and control, type W
Technical data 1/0-1/0-1/0 Bergen Aluminum XLPE URD triplex Direct Burial Cable
Phase conductor size: 1/0 AWG
Conductor thread: 19
Neutral conductor size: 1/0
Conductor thread: 19
Insulation thickness: 0,080 inches
External diameter: 1.133 inches
Allowable ampacity: direct burial: 215 amps
Allowable conduit ampacity: 180 amps
Weight: 0,465 pounds per foot
URD Cable Applications
1/0AWG Bergen Cable URD has a rated current capacity that depends on several factors, including ambient temperature, installation and specific conditions of use. However, 1/0AWG Bergen typically have a fairly high current rating due to their thickness and design.
The current capacity of a cable is determined taking into account the maximum allowable temperature of the conductor, heat dissipation capacity, and other safety factors. In general, This capacity is specified in tables provided by cable manufacturers or electrical engineering regulations..