CABLE NYY UNIPOLAR BIPOLAR TRIPOLAR TETRAPOLAR 0.6/1kV
What is CABLE NYY UNIPOLAR BIPOLAR TRIPOLAR TETRAPOLAR 0.6/1kV?
General application as power cable. In low voltage distribution networks, industrial facilities, in buildings and switchgear positions. In fixed installations, in indoor environments (on trays, canales, stapled, etc.); outdoors, in underground or directly buried conduits. Can be installed in dry and humid locations.
A, of the, three or four annealed copper conductors, solids, braided (pills, compacted or sectorial) or flexible. PVC insulation, with or without ground conductor (isolated) and PVC outer cover.
Characteristics Good electrical and mechanical properties. PVC outer jacket provides adequate acid resistance, fats, oils and abrasion. Facilitates splicing, derivations and endings. Flame retardant.
Tagged INDECO S.A. NYY (80°) 0,6/1 kV <Section> <Year> <Sequential measurement>
Norma(s) manufacturing NTP-IEC 60502-1
Calibers 6 mm² – 500 mm²
Packing in wooden coils, in required lengths.
Insulation colors (¹): Blanco, Negro, Rojo, Azul, Yellow. External cover: Negra.
NYY UNIPOLAR TECHNICAL DATA TABLE
SECTION | NUMBER OF WIRE | THICKNESSES | EXPECTED DIAMETER | EXPECTED WEIGHT | CURRENT CAPACITY (*) | |||
ISOLATION | DECK | BURIED | AIRE | DUCT | ||||
N° x mm² | mm | mm | mm | (Kg/Km) | A | A | A | |
1 x 6 | 7 | 1 | 1.4 | 7.9 | 112 | 72 | 54 | 58 |
1 x 10 | 1 | 1 | 1.4 | 8.5 | 150 | 95 | 74 | 77 |
1 x 16 | 7 | 1 | 1.4 | 9.7 | 222 | 127 | 100 | 102 |
1 x 25 | 7 | 1.2 | 1.4 | 11.3 | 330 | 163 | 131 | 132 |
1 x 35 | 7 | 1.2 | 1.4 | 12.3 | 431 | 195 | 161 | 157 |
1 x 50 | 19 | 1.4 | 1.4 | 13.9 | 568 | 230 | 196 | 186 |
1 x 70 | 19 | 1.4 | 1.4 | 15.6 | 778 | 282 | 250 | 222 |
1 x 95 | 19 | 1.6 | 1.5 | 18.1 | 1068 | 336 | 306 | 265 |
1 x 120 | 37 | 1.6 | 1.6 | 19.8 | 1323 | 382 | 356 | 301 |
1 x 150 | 37 | 1.8 | 1.6 | 21.6 | 1610 | 428 | 408 | 338 |
1 x 185 | 37 | 2 | 1.7 | 23.9 | 2007 | 483 | 470 | 367 |
1 x 240 | 37 | 2.2 | 1.8 | 26.9 | 2606 | 561 | 565 | 426 |
1 x 300 | 37 | 2.4 | 1.9 | 29.7 | 3243 | 636 | 646 | 480 |
1 x 400 | 61 | 2.6 | 2 | 33.1 | 4110 | 730 | 790 | 555 |
1 x 500 | 61 | 2.8 | 2.1 | 36.7 | 5118 | 823 | 895 | 567 |
NYY BIPOLAR TECHNICAL DATA TABLE
SECTION | NUMBER OF WIRE | THICKNESSES | EXPECTED DIAMETER | EXPECTED WEIGHT | CURRENT CAPACITY (*) | |||
ISOLATION | DECK | BURIED | AIRE | DUCT | ||||
N° x mm² | mm | mm | mm | (Kg/Km) | A | A | A | |
2 x 6 | 1 | 1 | 1.8 | 15.9 | 378 | 68 | 48 | 56 |
2 x 10 | 1 | 1 | 1.8 | 17.5 | 500 | 90 | 66 | 75 |
2 x 16 | 7 | 1 | 1.8 | 18.7 | 650 | 116 | 89 | 95 |
2 x 25 | 7 | 1.2 | 1.8 | 22 | 945 | 145 | 118 | 120 |
2 x 35 | 7 | 1.2 | 1.8 | 24 | 1210 | 175 | 145 | 145 |
NYY THREE-POLAR TECHNICAL DATA TABLE
SECTION | NUMBER OF WIRE | THICKNESSES | EXPECTED DIAMETER | EXPECTED WEIGHT | CURRENT CAPACITY (*) | |||
ISOLATION | DECK | BURIED | AIRE | DUCT | ||||
N° x mm² | mm | mm | mm | (Kg/Km) | A | A | A | |
3 x 6 | 7 | 1 | 1.8 | 16.2 | 428 | 56 | 41 | 45 |
3 x 10 | 7 | 1 | 1.8 | 17.7 | 587 | 75 | 57 | 60 |
3 x 16 | 7 | 1 | 1.8 | 19.8 | 815 | 99 | 76 | 80 |
3 x 25 | 7 | 1.2 | 1.8 | 23.3 | 1201 | 128 | 101 | 103 |
NYY TETRAPOLAR TECHNICAL DATA TABLE
SECTION | NUMBER OF WIRE | THICKNESSES | EXPECTED DIAMETER | EXPECTED WEIGHT | CURRENT CAPACITY (*) | |||
ISOLATION | DECK | BURIED | AIRE | DUCT | ||||
N° x mm² | mm | mm | mm | (Kg/Km) | A | A | A | |
4 x 16 | 7 | 1 | 1.8 | 21.5 | 1009 | 99 | 76 | 80 |
4 x 25 | 7 | 1.2 | 1.8 | 25.8 | 1522 | 128 | 101 | 103 |
4 x 35 | 7 | 1.2 | 1.8 | 28.4 | 1979 | 155 | 125 | 125 |
4 x 50 | 19 | 1.4 | 2 | 32.7 | 2637 | 184 | 151 | 149 |
4 x 70 | 19 | 1.4 | 2.1 | 36.8 | 3563 | 226 | 192 | 180 |
4 x 95 | 19 | 1.6 | 2.2 | 42.6 | 4863 | 272 | 232 | 217 |
4 x 120 | 37 | 1.6 | 1.8 | 45.3 | 5835 | 310 | 269 | 248 |
3×25/16 | 7 | 1.2 | 1.8 | 24.6 | 1381 | 128 | 101 | 103 |
3×35/16 | 7 | 1.2 | 1.8 | 27 | 1750 | 155 | 125 | 125 |
3×50/25 | 19 | 1.4 | 1.9 | 31.1 | 2361 | 184 | 151 | 149 |
3×70/35 | 19 | 1.4 | 2.1 | 35.2 | 3215 | 226 | 192 | 180 |
3×95/50 | 19 | 1.6 | 2.2 | 40.5 | 4324 | 272 | 232 | 217 |
3×120/70 | 37 | 1.6 | 2.4 | 44.5 | 5410 | 310 | 269 | 248 |
3×150/70 | 37 | 1.8 | 2.5 | 48.6 | 6452 | 348 | 309 | 278 |
3×185/95 | 37 | 2 | 2 | 52.8 | 7933 | 394 | 353 | 311 |
3×240/120 | 37 | 2.2 | 2.9 | 60.6 | 10451 | 458 | 415 | 361 |
Technical data of CABLE NYY UNIPOLAR BIPOLAR TRIPOLAR TETRAPOLAR 0.6/1kV
NYY cables are a type of power and control cable commonly used in fixed installations. They have copper conductors with insulation and PVC coating, making them suitable for indoor and outdoor applications, including underground and underwater facilities. The standard voltage rating of NYY cables is 0,6/1 kV.
The terms “unipolar”, “bipolar”, “tripolar” y “tetrapolar” refer to the number of conductors within the cable:
Unipolar: A single driver
Bipolar: two drivers
Tripolar: three drivers
Tetrapolar: four conductors
These configurations allow NYY cables to adapt to various electrical requirements, providing flexibility in power distribution and control applications.
When selecting a NYY cable, It is important to take into account factors such as the installation environment, specific mechanical protection needs and electrical parameters to ensure optimal performance and compliance with relevant standards.
CABLE Manufacturer NYY UNIPOLAR BIPOLAR TRIPOLAR TETRAPOLAR 0.6/1kV
NYY unipolar cable, bipolar, Three-pole and four-pole 0.6/1kV is widely used in fixed electrical installations for power distribution.. This type of cable is manufactured by various companies specialized in electrical conductors.. A prominent manufacturer of these cables is Dosense Cable, which specializes in the production of low and medium voltage cables.
NYY cables are designed with copper conductors, PVC insulation and cover, which gives them excellent weather resistance, humidity and underground environments. Its versatility allows it to be used both indoors and outdoors., including industrial and commercial environments.
Unipolar variants, bipolar, Tripolar and tetrapolar refer to the number of conductors they contain., allowing them to adapt to different electrical needs, from single-phase to three-phase power systems. Dosense Cable offers these cables with high quality, complying with international regulations and ensuring reliable performance in all types of installations.