N2XRY NA2XRY Cable
What is N2XRY NA2XRY Cable?
N2XRY NA2XRY Cable Definition and Construction
N2XRY NA2XRY is a type of electrical cable designed for use in various industrial and commercial environments. The designation can be broken down as follows:
N: Indicates that the cable is designed in accordance with the standards established by the National Electrical Code (NEC) the equivalent.
A: It means aluminum conductor, Does not show A, means copper conductor.
2X: Means the presence of cross-linked polyethylene insulation (XLPE).
R: steel wire armor(SWA Armoured)
Y: Indicates that the cable has a PVC jacket (polyvinyl chloride).
The wire N2XRY NA2XRY typically Copper Conductor or XLPE Insulated Aluminum Conductor. This insulation material is XLPE. PVC jacket provides additional protection against mechanical damage and environmental factors.
Structure of N2XRY NA2XRY
Conductor:
Material: Copper, bare or tinned. Aluminum
Type: Solid or braided.
Properties: High conductivity, flexibility and mechanical resistance.
Isolation:
Material: cross-linked polyethylene (XLPE).
Properties: High thermal resistance, electrical insulation and resistance to chemical attacks.
inner cover:
Material: PVC or similar materials.
Properties: Protection against mechanical damage.
Armor:
Type: steel wire armor (we proceed).
Function: Provides mechanical protection and anti-rodent features.
Outer sheath:
Material: PVC.
Properties: Protection against environmental factors and mechanical damage.
N2XRY NA2XRY Cable Construction
STRAIN | 0.6/1kV | |
CONDUCTOR | class stranded copper 2 | Class 2 Braided aluminum |
ISOLATION | XLPE (cross-linked polyethylene) | |
BED LAYER | PVC (polyvinyl chloride) | |
ARMOR | SWA (galvanized steel wire) | |
OUTER FLOOR | PVC (polyvinyl chloride) |

NYCY cable technical parameters
AWG | No. of cores x nominal cross-sectional area # x mm² | Driver type | Insulation thickness mm | Sheath thickness mm | Nominal Overall diameter mm | Cable weight kg/km |
4 | 1×25 | rm | 0.9 | 1.8 | 16.6 | 503 |
2 | 1×35 | rm | 0.9 | 1.8 | 17.7 | 612 |
1 | 1×50 | rm | 1 | 1.8 | 19.5 | 783 |
2/0 | 1×70 | rm | 1.1 | 1.8 | 21.5 | 1014 |
3/0 | 1×95 | rm | 1.1 | 1.8 | 23.5 | 1280 |
4/0 | 1×120 | rm | 1.2 | 1.8 | 26.0 | 1575 |
300mcm | 1×150 | rm | 1.4 | 1.8 | 27.5 | 1872 |
350mcm | 1×185 | rm | 1.6 | 1.8 | 30.0 | 2294 |
500mcm | 1×240 | rm | 1.7 | 1.9 | 33.0 | 2923 |
750mcm | 1×300 | rm | 1.8 | 2.1 | 36.0 | 3509 |
– | 1×400 | rm | 2 | 2 | 40.5 | 4534 |
– | 1×500 | rm | 2.2 | 2.3 | 45.0 | 5691 |
– | 1×630 | rm | 2.4 | 2.5 | 49.5 | 7267 |
– | 1×800 | rm | 0.7 | 1.8 | 56.5 | 9271 |
16 | 2×1.5 | re/rm | 0.7 | 1.8 | 13.6 | 325 |
14 | 2×2.5 | re/rm | 0.7 | 1.8 | 14.5 | 379 |
12 | 2×4 | re/rm | 0.7 | 1.8 | 15.7 | 448 |
10 | 2×6 | re/rm | 0.7 | 1.8 | 16.8 | 530 |
8 | 2×10 | rm | 0.7 | 1.8 | 19.4 | 783 |
6 | 2×16 | rm | 0.7 | 1.8 | 22.0 | 982 |
4 | 2×25 | rm | 0.9 | 1.8 | 25.5 | 1447 |
2 | 2×35 | rm | 0.9 | 1.8 | 28.0 | 1765 |
1 | 2×50 | rm | 1 | 1.9 | 30.5 | 2106 |
2/0 | 2×70 | rm | 1.1 | 2 | 35.0 | 2765 |
3/0 | 2×95 | rm | 1.1 | 2..2 | 39.5 | 3746 |
4/0 | 2×120 | rm | 1.2 | 2.3 | 43.5 | 4465 |
300mcm | 2×150 | rm | 1.4 | 2.5 | 47.5 | 5303 |
350mcm | 2×185 | rm | 1.6 | 2.6 | 54.0 | 6890 |
500mcm | 2×240 | rm | 1.7 | 2.8 | 59.5 | 8463 |
750mcm | 2×300 | rm | 1.8 | 3.1 | 65.0 | 10151 |
16 | 3×1.5 | re/rm | 0.7 | 1.8 | 14.1 | 351 |
14 | 3×2.5 | re/rm | 0.7 | 1.8 | 15.1 | 415 |
12 | 3×4 | re/rm | 0.7 | 1.8 | 16.3 | 503 |
10 | 3×6 | re/rm | 0.7 | 1.8 | 17.5 | 603 |
8 | 3×10 | rm | 0.7 | 1.8 | 20.5 | 903 |
6 | 3×16 | rm | 0.7 | 1.8 | 23.0 | 1161 |
4 | 3×25 | rm | 0.9 | 1.8 | 27.0 | 1709 |
2 | 3×35 | rm | 0.9 | 1.8 | 29.5 | 2127 |
1 | 3×50 | sm | 1 | 1.9 | 31.5 | 2424 |
2/0 | 3×70 | sm | 1.1 | 1.9 | 36.5 | 3438 |
3/0 | 3×95 | sm | 1.1 | 2 | 40.0 | 4343 |
4/0 | 3×120 | sm | 1.2 | 2.2 | 43.5 | 5172 |
300mcm | 3×150 | sm | 1.4 | 2.3 | 49.5 | 6675 |
350mcm | 3×185 | sm | 1.6 | 2.5 | 54.0 | 7977 |
500mcm | 3×240 | sm | 1.7 | 2.6 | 60.0 | 9995 |
750mcm | 3×300 | sm | 1.8 | 2.8 | 65.0 | 11990 |
16 | 4×1.5 | re/rm | 0.7 | 1.8 | 14.9 | 395 |
14 | 4×2.5 | re/rm | 0.7 | 1.8 | 16.0 | 470 |
12 | 4×4 | re/rm | 0.7 | 1.8 | 17.4 | 575 |
10 | 4×6 | re/rm | 0.7 | 1.8 | 19.5 | 798 |
8 | 4×10 | rm | 0.7 | 1.8 | 22.0 | 1058 |
6 | 4×16 | rm | 0.7 | 1.8 | 25.5 | 1518 |
4 | 4×25 | rm | 0.9 | 1.8 | 29.0 | 2055 |
2 | 4×35 | rm | 0.9 | 1.9 | 32.0 | 2585 |
1 | 4×50 | sm | 1 | 2 | 35.5 | 3040 |
2/0 | 4×70 | sm | 1.1 | 2.1 | 41.0 | 4305 |
3/0 | 4×95 | sm | 1.1 | 2.2 | 45.0 | 5476 |
4/0 | 4×120 | sm | 1.2 | 2.4 | 51.5 | 7064 |
300mcm | 4×150 | sm | 1.4 | 2.5 | 57.5 | 8536 |
350mcm | 4×185 | sm | 1.6 | 2.7 | 61.5 | 10189 |
500mcm | 4×240 | sm | 1.7 | 2.8 | 68.0 | 12772 |
750mcm | 4×300 | sm | 1.8 | 3 | 73.5 | 15380 |
16 | 5×1.5 | re/rm | 0.7 | 1.8 | 15.8 | 441 |
14 | 5×2.5 | re/rm | 0.7 | 1.8 | 17.0 | 535 |
12 | 5×4 | re/rm | 0.7 | 1.8 | 19.3 | 768 |
10 | 5×6 | re/rm | 0.7 | 1.8 | 21.0 | 921 |
8 | 5×10 | rm | 0.7 | 1.8 | 23.5 | 1235 |
6 | 5×16 | rm | 0.7 | 1.8 | 27.0 | 1765 |
4 | 5×25 | rm | 0.9 | 1.8 | 31.5 | 2423 |
2 | 5×35 | rm | 0.9 | 1.9 | 34.5 | 3057 |
1 | 5×50 | rm | 1.1 | 2.2 | 40.0 | 4099 |

N2XRY NA2XRY Cable Application Areas
1 Nominal voltage
Nominal voltage: N2XRY and NA2XRY cables typically have a voltage rating of 0,6/1 kV, indicating its suitability for low and medium voltage applications.
Application: This voltage rating makes N2XRY and NA2XRY cables ideal for use in residential installations, commercial and light industrial.
2 Nominal temperatures
Operating temperature: N2XRY NA2XRY cables can operate effectively within a temperature range of -15°C to +70°C. This wide range allows flexibility in various environmental conditions.
short circuit temperature: The cables are designed to withstand short circuit conditions with temperatures up to +250°C, ensuring reliability even under fault conditions.
3 Electrical properties
insulation resistance: High insulation resistance of XLPE ensures minimal leakage currents and efficient cable performance. This property is crucial to maintain the integrity of the system and avoid electrical risks..
Driver resistance: N2XRY NA2XRY cables' copper conductors offer low resistance, helping to reduce energy losses and improve overall efficiency.
4 Mechanical properties
Flexibility: Stranded copper and aluminum conductors offer excellent flexibility, making the N2XRY NA2XRY cable suitable for installations in tight or complex spaces.
Warp radio: The minimum bend radius of N2XRY NA2XRY cables is usually 10 times the diameter of the cable, ensuring the cable can be installed without risk of damaging the insulation or conductor
N2XRY NA2XRY cable manufacturer
Dosense Cable is proud to be a leading manufacturer and supplier of N2XRY NA2XRY, Recognized for superior performance and reliability in demanding environments. Thanks to our state-of-the-art production facilities and rigorous quality control processes, Dosense Cable guarantees that all N2XRY and NA2XRY cables meet the highest industry standards.
Our N2XRY cables are designed for a wide range of industrial and commercial applications, offering robust protection with cross-linked polyethylene insulation (XLPE) and a durable PVC cover. Ideal for environments where durability and reliability are essential, N2XRY cables excel in power distribution, industrial facilities and commercial buildings.
In Dosense Cable, We are committed to offering excellence in all the cables we produce. Our dedicated team of experts works tirelessly to ensure that our products not only meet your expectations, but they overcome them. Choose Dosense Cable for your N2XRY and NA2XRY needs and experience quality, Unmatched reliability and performance in every project.